473-FA6
Wahyu Adi TrionoProblem: Issue high vibration motor at FS and LS
Action:
Check found tank of AUTO grease low level, replace tank of AUTO grease motor with spare unit. Add grease motor at FS and LS around 15 times, measure vibration motor result 1.7 mm/s and 2.9 mm/s ( EDI & ADI )
Status: done